Residential

  1. Can I control my DM32 over Ethernet and still plug the DM32 USB into a computer for power?

    In order to do both, you need to be sure you have version 5.8.30 of FanTestic or later. 

    In all versions of FanTestic before version 5.8.30,  if you plugged a DM32 into a computer USB to give it power (instead of plugging into the wall adapter) FanTestic would assume you also wanted to use USB Serial connection for control.  FanTestic made this assumption even if the gauge was also connected to the computer over Ethernet (via the Network cable or via WiFi). 

    In all versions starting with 5.8.30, FanTestic discovers gauges connected via Ethernet first, so it can ignore the same gauge also found on USB Serial. 

    This change allows users to have their DM32 connected for control via Ethernet but also connect the DM32 to the computer USB port for power (if it is more convenient than connecting to a wall outlet).  Retrotec recommends that users use Ethernet connection rather than USB for controlling the DM32. 

    Read more »
  2. What are the power requirements for Retrotec Calibrated Fans?

    *Max current is initial in-rush current. Generators used for Retrotec equipment should be inverter type generators, (i.e., suitable for use with sensitive electronics).

    Voltage (VAC) Max current (A) Power (W)
    3000 (3 Phase Drive) 120 22 2640
    208 13 2704
    230 10.5 2415
    240 10.3 2472

    ***** Minimum generator power output should be 3000W *****

    1000 Calibrated Fan 120 23 2760
    208 11 2288
    Read more »
  3. Why does FanTestic default to taking 10 or more readings when the Standard only requires 5?

    Retrotec recommends you take the maximum number of test points to decrease the uncertainty in your test.

    Yes, you can change this default and take only 5 readings according to the Standard but your uncertainty will often be too high and you might have to retest.  Next, you might retest and find the result differs from the previous test by 10% or more making you lose confidence in the results. Retrotec defaults that include taking 10 test points and longer baselines will optimize your tests and give better results. 

    You might save a few minutes by testing to the minimum allowed by the Standards but in the long run, your test results will be poor. Officials look at high uncertainties and poor repeatabilities between your tests and wrongly conclude your equipment is faulty but the truth is that your test method is faulty.  Please use our defaults as practical minimums and if anything take your tests over a longer time rather than shorter and your results will

    Read more »
  4. How can I improve uncertainty of test results?

    Click the "Reset to Standard Default" button in the Advanced settings menu, to ensure default program parameters are used.

    Read more »
  5. What are the manufacturer's recommendations for equipment calibration?

    Our manufacturer's recommendation for calibration is as follows:

    • Retrotec fans: Every 5 years.  
    • DM-2 Manometer: Every 2 years  or if the Manometer fails a field check. 
    • DM32 / DM32 WiFi Manometer: Every 5 years or if the Manometer fails a field check.

    Please review the DM32 and DM-2 Manuals on how to perform a field check.  

    This only covers our manufacturer recommendation.  The energy standards (EN13829, ASTM, ATTMA, USACE, etc...) that you are using for test results may have different calibration intervals.  Please consult the energy standards for the specific equipment calibration intervals.

    Read more »
  6. Why does my gauge show two dashes “—“?

    Fan Pressure (flow pressure) is too low for the Range, which means you should change to a smaller more restrictive Range to increase fan pressure.
     

    Read more »
  7. What is the flow range (in units of CFM) for the 5000/6000 fan's range configurations?

    500 Flow Chart

    6000 flowchart

    Read more »
  8. When I try to install FanTestic or Integrity, I get the error "Cannot Start Application" and it says "Cannot continue. The application is improperly formatted. Contact the application vendor for assistance."

    Answer

    If this is the Error you are seeing:

    Click on the "Details" button to get more information.  In the summary, you will see:

    ERROR SUMMARY:  "+ Your Web browser settings do not allow you to run signed applications." 

    This error summary indicates that there are security settings in your web browser  that are preventing the application from being able to download. 

    Some people have had success by adding http://retrotec.com to their "Trusted Sites"  in the Tools>>Internet Options>>Security settings

    Read more »
  9. How do I know how many fans I need for a Blower Door or Enclosure Integrity Test?

    I have a Energy or Enclosure Integrity Test to perform.  How many fans do I need to properly run the test?  Do I have enough fans to run the test?

    We have created two tools to help you figure out how many fans you will need for your test. 

    Download either the Blower Door or Enclosure Integrity version of the Number of Fans Calculator

    Next, open the file in excel and "Enable Editing" when a security warning appears.

    Fill in all the fields highlighted in blue.  The number of fan results are highlighted in green.

    Here is what the Blower Door Number of Fans Calculator looks like:

    And this

    Read more »