Double Hi-Power
This system is actually two complete US6112F systems that can be used independently or combined with the Leakage Split kit for ceiling neutralization. Includes two 1 hp calibrated fans making it Ideal for large size enclosures up to 102,000 ft3/ 2,900 m3 for Inerts and 212,000 ft3/ 6,000 m3 for halocarbons. Includes fan cases and tool cases.
It also includes the newly released, industry changing DM32X gauge.
Double hi-power fans offers a huge advantage. Not only in the maximum size you can test; probably any enclosure. But also enough power to test large dampers while installed. The high power fans will test their ability to open and then accurately measure the entire relief vent pathway to ensure the peak pressure specifications are not exceeded.
Test for hold times in flooded volumes up to 102,000 cu ft (2000 m3) for Inert agents and 140,000 cu ft (4000 m3) for halocarbon chemical agents.
This system will test the venting for a volume up to a maximum of 24,000 cu ft (660 m3) for Inert agents although vents up to 16 sq ft (1.6 m2) can be measured individually.
Request literature on all of Retrotec systems to determine the size of enclosures that can be tested with each system.
Why Retrotec for Enclosure Integrity?
All Retrotec systems include tech support from Retrotec who originated the idea of Enclosure Integrity testing in 1984. They promoted it within NFPA and in 1986 wrote the first Enclosure Integrity standard. Retrotec has been the lead researcher for enclosure testing ever since. Every major clean agent system manufacturer worldwide relies on Retrotec’s expertise for both hold time and peak pressure predictions.
2 x DM32X Gauge Package
- DM32X Gauge (Newly Released! click here for details)
- USB-C Charging Cable
- Cat5 Cable
- Gauge Case
- DM32X Magnetic Clip
- ISO17025 calibration of DM32X
- Gauge Calibration Verification Report
-
Each
fan set contains:
- 6000 Series Calibrated Fan
- High Power Drive for 6000 Series Fan (120V/60Hz, 240V/50Hz, or 110V/50Hz)
- Range Ring A for 5000/6000 Series Fan
- B8 Plate for 5000/6000 Series Fan
- 8 x 4" Blank Plugs
- Ranges 74, 47, & 29
- 2 x Fan Cover
- System Calibration Verification Report
- Large 50" Aluminum Frame
- Large #5 Crossbar
- 3 x Fan Crossbar Strap for Aluminum Frame
- Single Door Cloth
- Large Roll Up Cloth Case
- 2 x Large #6 Crossbar
- 1000/5000/6000 Flex Duct
- Flex Duct Fill-In Sheet
- Subfloor test panel for Model 2000/3000 Fans
- Field Calibration Plate for Modular Panel
- Flex Duct Case with Shoulder Strap
2 x Hard Panel Set for 1000/5000/6000 Series Fan
2 x Case for System Accessories
Specifications below are for each individual fan. Model 6000 Fan |
||||
|
Flow Into: |
CFM |
Litres/sec |
M3/h |
Max Flow, per fan (60 Hz) |
Free Air |
8,100 |
3,823 |
13,762 |
50 Pa |
7,700 |
3,634 |
13,082 |
|
75 Pa |
7,400 |
3,492 |
12,573 |
|
Minimum Flow: on Range B29 |
50 Pa |
9 |
4 |
15 |
Dimensions: |
26" × 25.5" × 9.5" (66 x 65 x 24 cm) |
|||
Weight: |
36.3 lb (16.5 kg) or 38 lb (17.2 kg) with Ring A & Plated B8 installed |
|||
Flow Accuracy: |
+/-5% |
|||
Power: |
120V@60hz/22.0A or 240V@50hz/10.9A or 110V@50Hz/22.0A |
|||
Recommended Fan Calibration Interval: |
5 years |
Digital Gauge Model: |
DM32X |
Gauge Specs: |
Door Panel and Frame Model: |
PN201 |
Type of Panel: |
Hard Panel - Single 1000/3000/5000/6000 Fan |
* The max flow of the fan will vary depending on the following factors: Voltage, frequency, barometric pressure, back pressure, blade pitch, air temperature, bearing tightness, inlet air turbulence
* 5000/6000 series blower doors DO NOT work with the DM-2 digital gauge