Small Enclosure Integrity Testing
For those who want to test small enclosures and don’t want to invest a lot in larger equipment. Small enough to transport on a plane to test in remote places.
Test for hold times in flooded volumes up to 4,000 cu ft (120 m3) for Inert agents and 8,000 cu ft (240 m3) for halocarbon chemical agents.
Testing pressure relief vents will require more power. This system will test the venting for a volume up to 1,000 cu ft (40 m3) for Inert agents.
It also includes the newly released, industry changing DM32X gauge.
Request literature on all of Retrotec systems to determine the size of enclosures that can be tested with each system.
Why Retrotec for Enclosure Integrity?
All Retrotec systems include tech support from Retrotec who originated the idea of Enclosure Integrity testing in 1984. They promoted it within NFPA and in 1986 wrote the first Enclosure Integrity standard. Retrotec has been the lead researcher for enclosure testing ever since. Every major clean agent system manufacturer worldwide relies on Retrotec’s expertise for both hold time and peak pressure predictions.
1 x DM32X Gauge Package
- DM32X Gauge (Newly Released! click here for details)
- USB-C Charging Cable
- Cat5 Cable
- Gauge Case
- DM32X Magnetic Clip
- ISO17025 calibration of DM32X
- Gauge Calibration Verification Report
- 300 Series Fan
- DC Power Supply for 300 Series Fan
- 300 Series Fan Power Cord With Plug
- Control Panel for 300 Series Fan
- End Plate 300 - Range 102
- 300 Blower Door Case
- Fan Fit & Calibration
- Certificate for Fan Fit & Calibration
- Ranges 74,47 and 29
- Aluminum Frame, Red Anodized
- Cloth for 200/300 Series Fan, Regular Height
- Fan Crossbar Strap for Aluminum Frame
- Case for Aluminum Frame
Fan Model # |
300
|
|||
Flow Into: |
CFM |
liters/sec |
m3/h |
|
Maximum Flow, CFM |
Free Air |
803 |
379 |
1365 |
25 Pa |
783 |
370 |
1331 |
|
Minimum Flow |
Range 102 |
174.4 |
82.3 |
296.3 |
Range 74 |
30.1 |
14.2 |
51.1 |
|
Range 47 |
11.3 |
5.3 |
19.1 |
|
Range 29 |
5.2 |
2.4 |
8.7 |
|
Range 18 |
3.2 |
1.5 |
5.5 |
|
Range 11 |
TBD |
TBD |
TBD |
|
Dimensions |
14" × 12.5" × 14.5" (35.5 x 32 x 37 cm) |
|||
Weight |
12 lb (5.5 kg) |
|||
Flow Accuracy |
+/-3% ISO 17025 accredited certificate available |
|||
Power Supply |
Input: 120V/60Hz, 240V/50Hz, or 110V/50Hz Output: 48V DC/ 3.31A |
|||
Power Output |
0.213 hp, 159 Watts |
|||
Maximum Fan Calibration Interval |
Every 5 years or sooner depending on standard |
|||
Digital Gauge Model |
DM32X |
* The max flow of the fan will vary depending on the following factors:
barometric pressure, back pressure, blade pitch, air temperature, bearing tightness, inlet air turbulence, length of flex duct
Digital Gauge Model: |
DM32X |
Link to Specifications: |
Door Panel and
|
AL257 |
Type of Panel: |
Regular Sized Cloth Panel for 200/300 Series Fan |
Door Panel and Frame Model: |
AL250 |
Type of Frame: |
Regular Sized Red Anodized Frame |
Collapsed: |
27 1/8” X 53 3/8” (68.9cm X 135.6cm) |
Expanded: |
43 5/8” X 97 ½” (110.8cm X 247.6cm) |
Frame Thickness: |
1.75” (5.3 cm) |
* The max flow of the fan will vary depending on the following factors:
barometric pressure, back pressure, blade pitch, air temperature, bearing tightness, inlet air turbulence, length of flex duct
* 5000/6000 series blower doors DO NOT work with the DM-2 digital gauge