Multiple Flow Pressure Relief Vents

In stock

SKU
PV

* Required Fields

The PV range of dual acting pressure relief vents is a new development in the world of pressure relief vents for gaseous extinguishing system. The vents are gravity balanced for fool proof operation, and apart from that the vents are designed to provide a great validated efficiency factor of free vent area at all pressures. The pressure vent blades start to open at above 60 to 80 Pascal’s and is designed to be fully open at 125 Pascal’s pressure in both directions. The special design provides more than 75% free vent area at 125 Pascal’s room pressure, which is measured at the mentioned reference pressure. This means you need less vents, smaller holes, less builders work, smaller vents, and we now provide a greater size range.

The range comes with a 2 hour fire rating to EN1364-1 including certification, as well as verification of its operation. Detailed measurement reports are available upon request.

The PV range is supplied in two kits. One for internal use and one for external use. The PV vent only is used for internal and the PV vent with a louvre is used for external venting. As the vent opens in both directions the external louvre can be provided in a fixed blade louvre or dynamic (more weather proof) louvre.

When mounting the PV range in doors or narrow walls the external wall flange is used as a cover trim.

Multiple Sizes Available. Choose From:

  • 350 x 150 mm Dual Flow Vent
  • 350 x 300 mm Dual Flow Vent
  • 450 x 450 mm Dual Flow Vent
  • 600 x 600 mm Dual Flow Vent
  • 750 x 750 mm Dual Flow Vent
  • 1050 x 1050 mm Dual Flow Vent
Pressure Relief Vent Specifications
Pressure Relief Vent Diagram
← Scroll horizontally to view all columns →
Vent size in mm PV150 PV300 PV450 PV600 PV750 PV1050
A 350 350 450 600 750 1050
B 150 300 450 600 750 1050
C 500 500 600 750 900 1200
D 300 450 600 750 900 1200
E 570 570 670 820 970 1270
F 318 468 618 768 918 1218
Regular wall
thickness (order
sleeve for thicker
walls)
110 - 240 110 - 240 110 - 240 110 - 240 110 - 240 110 - 240
Wall opening size 430W x 175H 430W x 325H 530W x 475H 680W x 625H 830W x 775H 1130W x 1075H
FVA @125Pa 0.036m²
55.8in²
0.073m²
113.15in²
0.151m²
234.05in²
0.27m²
418.5in²
0.42m²
651in²
0.82m²
1271in²
Fire Rating 180 Minutes 180 Minutes 120 Minutes 120 Minutes 120 Minutes 120 Minutes
Default opening pressure 80 Pascals 80 Pascals 60 Pascals 80 Pascals 100 Pascals 80 Pascals
Default finishing coating RAL9016 powder RAL9016 powder RAL9016 powder RAL9016 powder RAL9016 powder RAL9016 powder

Note: Provides a high free flowing vent area, lab verified. The default opening pressure is set to 60-80Pa.




1 (855) 738-7683

Talk with a Sales Rep