FanTestic – Test Sheet

FanTestic

Go step by step through a test sheet, learn how to set it up and input information.https://youtu.be/FYmu77RbY9I

Starting a New Test

  • Click File → New test or use the “New test” button to begin.

  • Verify the test standard selected (e.g. ASTM, ATTMA, EN13829) matches your project requirements (found under Tools → Options for defaults).

Equipment and Calibration Data

  • Fan Model & Serial Number: Select and enter your fan; press the wrench icon to open the calibration dialog and input fan-specific flow coefficients.

  • Gauge Info: Add your digital gauge (e.g., Retrotec DM‑2 or DM‑32), then use the wrench icon to enter its calibration corrections.

Building Data & Environmental Conditions

  • Building Dimensions: Input floor area and envelope area per standard.

  • Location & Weather: Enter operator location (inside/outside), temperature, barometric pressure, wind speed, and wind direction.

  • Bias/Baseline Pressure: Record initial and final baseline readings to capture natural pressure offsets.

Test Settings & Data Sets

  • Adding Data Sets: Use the New Set button to compare tests (e.g., pre- and post-seal). Remove or clear sets as needed.

  • Pressure Points: Manually enter induced pressure levels (10–60 Pa typically) or let the software set them in Auto/Semi-Auto mode.

  • Fan Pressure Lines: You can have multiple lines if you change flow range plates mid-test. Each one corresponds to fan + range.

Running the Test

  • Manual Entry vs. Auto: Switch between “Enter data manually” or enable automatic data capture. Auto disables manual edits.

  • Range Changes: FanTestic will prompt if flow is too low or fan maxes out, pausing for range adjustments. Manually select new range if needed.

Final Results and Reporting

  • After inputting sufficient points, the software calculates leakage metrics, air change rates, curve coefficients, and compliance with deviation checks.

  • Save & Export:

    • Use Save As to label test files.

    • Generate reports in Word or export raw data to Excel.

    • Print screenshots via File ➝ Print from the screen view.

Why this Matters

  • Complete & accurate inputs ensure reliable results and compliance.

  • Built-in calibration steps boost measurement precision.

  • Auto/Semi-Auto flexibility caters to different testing needs.

  • Professional output streamlines reporting and client delivery.

Pro Tips

  • Always confirm your test standard and saved settings before starting.

  • Keep fan and gauge calibration data up-to-date in the wrench dialogs.

  • Use baseline bias values to measure natural infiltration influence.

  • Name data sets and files clearly for later reference.