Model 5120F Fire [Enclosure Integrity]
Includes the newly released DM32X Gauge
Model 5120F with Hard Panel
The Model 5120F with Hard Panel delivers the same reliable performance as the Model 5100F cloth panel system but includes modular hard panels for a quick setup and a professional appearance. Designed for efficiency and durability, this system enhances testing operations with a sturdy and adaptable framework.
This package includes a fan case, tool case, and a large aluminum frame with a cloth panel, ensuring secure setups in tight enclosures. It also features the newly released, industry-changing DM32X gauge, providing precision and ease of use for enclosure integrity testing.
Why Choose Retrotec for Enclosure Integrity Testing?
Retrotec pioneered the concept of Enclosure Integrity testing in 1984 and has remained the industry leader ever since. By promoting it within NFPA and authoring the first Enclosure Integrity standard in 1986, Retrotec set the foundation for modern testing methods. As the leading researcher in enclosure testing, Retrotec provides unparalleled expertise, with every major clean agent system manufacturer worldwide relying on its technology for hold time and peak pressure predictions. All Retrotec systems come with expert technical support, ensuring professionals have the guidance they need for accurate and efficient testing.
1 x 5000 Series Fan Set
- 5000 Series Calibrated Fan
(120V/60Hz, 240V/50Hz, or 110V/50Hz) - Range Ring A
- B8 Plate
- 8 x Blank Range Plugs
- Blower Door Tubing Kit
- Tubing Umbilical
- Fan Cover
- Power Cord
- System Calibration Verification Report
1 x Hard Panel Set
1 x Large SmartCloth™ Door Panel & Frame
- Large SmartCloth™ Wind Dampening Cloth Door
- Large Aluminum Frame, Etched with Sizing Markings
- Traveling Case
1 x DM32X Gauge Package
- DM32X Gauge
- Gauge Case
- USB-C Charging Cable
- Cat5 Cable
- ISO17025 calibration of DM32X
- Gauge Calibration Verification Report
1 x System Accessories Case
1 x Fan Case
4 x Roll of Grill Masks
| Model 5000 Fan | ||||
| Flow Into: | CFM | Litres/sec | M3/h | |
| Max Flow, per fan (60 Hz)
Reduces values by 15% for 50Hz fan |
Free Air | 6,400 | 3,020 | 10,874 |
| 50 Pa | 5,700 | 2,690 | 9,684 | |
| 75 Pa | 5,400 | 2,549 | 9,175 | |
| Minimum Flow: | ||||
| on Included Range B1 | 50 Pa | 111 | 52 | 188 |
| on Optional Range 74 | 50 Pa | 37 | 17 | 63 |
| on Optional Range 47 | 50 Pa | 21 | 10 | 35 |
| on Optional Range 29 | 50 Pa | 9 | 4 | 15 |
| Dimensions: | 22″ (55.9 cm) inlet diameter, 9.75″ (24.8 cm) long, 25″ (63.5 cm) height | |||
| Weight: | 33.5 lb (15.2 kg) or 35.2 lb (16.0 kg) with Ring A & Plated B8 installed | |||
| Flow Accuracy: | +/-5% | |||
| Power: | 120V@60hz/11A or 240V@50hz/4.9A or 110V@50Hz/ 8.9A | |||
| Recommended Fan Calibration Interval: | 5 years | |||
| Digital Gauge Model: | DM32X (Click Here) | |||
- Ahj Verification Form Nfpa218.5 KB
- Enclosure Integrity Pretest Checklist Form180.9 KB
- Enclosure Integrity Room Size Estimates30.9 KB
- Enclosure Test Form Guide1.1 MB
- Manual Blower Door Operation 300 5000 6000 70003.6 MB
- Manual DM32 Configurator Software786.5 KB
- Manual DM32 Data Logger1.6 MB
- Manual Dm32 Operation 1 16.7 MB
- Manual DM32 Virtual Gauge1.5 MB
- Manual DM32X Operation3.8 MB
- Manual Fire FanTestic Integrity EN3.5 MB
- Manual Fire FanTestic Integrity ISO3.7 MB
- Manual Fire FanTestic Integrity NFPA3.7 MB
- Manual Fire FanTestic Integrity Venting Calculator1.7 MB
- QuickGuide DM32 Operation804.4 KB
- QuickGuide DM32X Operation4.6 MB
- QuickGuide Blower Door With DM32X For Model 300 5000 6000 70008.7 MB
- QuickGuide Blower Door Range Configuration For 5000 600011.0 MB
- QuickGuide Blower Door With DM32 For Model 5000 60002.5 MB
- QuickGuide Door Panel Cloth Folded Version3.6 MB
- Sample ISO Accredited Gauge Calibration Certificate140.2 KB