The Next Generation Nearly a decade ago, our beloved DM32 became the industry's first manometer with smart capabilities, wireless connectivity, and a touch screen interface. Its accuracy, durability, and ease-of-use made it the industry's favorite gauge. While still keeping your favorite DM32 features such as an ergonomic design and color-coded ports, we have now re-engineered it with all new technology, features, and abilities. Meet the DM32X: air tightness testing and building diagnostics will never be the same again. This refreshing new testing experience will open new doors and extend your diagnostic abilities.

1 x DM32 WiFi Digital Gauge Package

  • DM32 WiFi Dual Channel Color Touchscreen Manometer
  • USB Cable, 7' (2.1 m)
  • Cat5 Cable, 7' (2 m) Blue
  • DM32 USB Charging Module (120V/60Hz, 240V/50Hz, or 110V/50Hz)
  • DM32 Software Suite (Virtual Gauge, DM32 Configurator, Data Logger, and DM32 USB driver)
  • Gauge Case
  • DM32 Magnetic Clip
  • ISO17025 calibration of DM32
  • Gauge Calibration Verification Report

Specifications for Digital Gauge Model:

DM32W

   

Dimensions:

5.8" × 3.6" × 1.4" (14.7 × 9.2 × 3.5 cm)

   

Weight:

12 oz (340 g)

   

Power:

4200 mAh LiPoly rechargeable battery.  Integrated on board charging circuit.

Up to 11 hours battery life on a single charge.

(Battery life and charge cycles vary by use and settings; actual results will vary.)

   

Screen type:

QVGA Color touchscreen LCD display

   

Screen dimensions:

3.2” (8.2 cm) diagonal, 2.6" × 1.9" (6.6 × 5.0 cm)

   

Microcontroller:

32 bit

   

Pressure channels:

2 independent pressure channels (“A” & “B”)

   

Pressure sensor type:

Digital

   

Pressure range:

 

DM32-10A (current version)

-2,488 Pa to +2,488 Pa (-10 to +10 in W.C.)

 

DM32-4A (no longer sold)
-995 Pa to +995 Pa (-4 to +4 in W.C.)

 

DM32-20A (current version for commercial ductesters)
-4,976 Pa to +4,976 Pa (-20 to +20 in W.C.)

 

* DM32-20A started shipping Jan 2015

* DM32-10A started shipping Oct 2017

 

   

Pressure resolution:

0.1 Pa (0.004 in WC, 0.002  psf)

   

Pressure accuracy:

DM32-10A (current version)
+/- 0.4% of pressure reading or +/- .07 Pa @ 22 degree (C)

+/- 0.6% of pressure reading or +/- .15 Pa @ 0 – 44 degree (C)

+/- 0.9% of pressure reading or +/- 1 Pa @ 70 degree (C)

 

DM32-4A (no longer sold)
±1% of pressure reading or ±0.25 Pa (whichever is greater)

 

DM32-20A (current version for commercial ductesters)
±1% of pressure reading or ±1.0 Pa (whichever is greater) 

   

Pressure accuracy calibration meets:

USACE, ASTM E779, CGSB-149.10, EN 13829, UK ATTMA TSL1 and TSL2, NFPA 2001, ISO 14520, EN15004, ISO9972

 

the DM32-20A does not meet these standards and is meant to be used for high pressure testing where 1 Pa or 1%  is adequate accuracy

   

Temperature Ranges:

Compensated:
32°F to 158°F (0°C to 70°C)

Operating Storage: 
-13°F to 185°F  (-25°C to 85°C)
-40°F to 257°F  (-40°C to 125°C)

   

Humidity Limits
(non condensing)

0 to 95% RH

   

PC Connectivity options (MS Windows only):

Ethernet (direct or over network), USB (direct), Wireless via WiFi

   

WiFi 802.11 protocols:

b/g/n

   

Recommended calibration interval:

Every 5 years

   

 

Supported Units of Measurement and Results

Channel A:

Pressure: Pa, psf, or in WC

Channel B:

Pressure: Pa, psf, or in WC

Flow:  CFM, L/s, m3/s, m3/h

Flow/Area (Permeability):  CFM/sq ft, CFM/100 sq ft, CFM/1000sq ft, (m3/h)/m2, (L/s)/m2

Air changes per hour:  /h

Equivalent leakage area,  “EqLA”: sq ft, sq in, cm2

Effective leakage area,  “EfLA”: sq ft, sq in, cm2

 

*Results can be extrapolated to any desired test pressure

The following results are already extrapolated to the stated reference pressure:

 

  • Equivalent leakage area extrapolated to 10 Pa, “EqLA10”:  sq ft, sq in, cm2
  • Equivalent leakage area per enclosure area at 10 Pa,  “EqLA10/area”: sq ft/sq ft, sq in/sq ft, sq in/100sq ft, cm2/m2)
  • Effective leakage area extrapolated to 4 Pa,  “EfLA4”: sq ft, sq in, cm2
  • Effective leakage area per enclosure area at 4 Pa, “EfLA4/area”: (sq ft/sq ft, sq in/sq ft, sq in/100sq ft, cm2/m2)